2.
In the Device configuration editor under Communication Settings tab, click the
Gateway drop-down button and then click Manage gateways ….
Manage_Gateways.png
Figure 3.3.4-2 Manage Gateways
3.
In the Manage gateways window, click Add to add a Gateway using the IP Address
of the COM600 being used. Click OK to close the window. Do this only if the
desired Gateway is not available in this dialog already.
4.
In the Device configuration editor under Communication Settings tab, click Scan
Network…. The Select Device window opens and shows the “Logic Processor”
device available in COM600. The Logic Processor item displayed under Gateway
is typically identified by COM600 Computer Name.
5.
Select the node showing COM600 Computer Name and click OK. This sets the
active path between Logic Editor and Logic Processor, allowing further PLC
Application download possible.
If the Logic Processor does not show up under gateway,
then there could be a possible firewall rule blocking the
connection from Logic Editor to Logic Processor. Check
the Inbound rules defined in COM600 Windows Firewall.
The rules specific to Logic Processor can be further
identified by looking for “Gateway Service” as the rule
name in Windows Firewall configuration.
21
COM600 series 5.1
1MRS756738
Logic Processor User's Manual