Description
Value or Value range/ Default
Property / Para-
meter
The number of padding characters inser-
ted to the end of telegram to delay the
resetting of RTS signal.
0...255
Default: 0
RTS Keepup Pad-
ding Characters
Delay in milliseconds between receiving
CTS signal and start of transmission.
0...65535
Default: 15
Transmission Wait
Delay
Configuring Device Properties
3.4.4.
Configuring IEC101 Device properties
3.4.4.1.
Table 3.4.4.1-1 lists the configurable properties for IEC101 Device and value ranges for
these properties. The actual configuration by using SAB600 is performed as described
in 3.4.1, General about configuring objects.
Table 3.4.4.1-1 IEC101 Device properties
Description
Value/Value range
Name
Basic
Specifies whether diagnostic
AE events are sent for the sta-
tion or not.
True
False
Default: False
Diagnostics Enabled
Specifies whether redundant
channel is used or not.
True
False
Default: False
Has Redundant Line
Controls whether the station
communication is initially in use
or not.
In use
Not in use
Default: In use
In Use
Addresses
27
Station Automation COM600 3.4
1MRS755382
IEC 60870-5-101 Slave (OPC) User's Manual