CBV-2U4-3T(-N) |
Appendix : List of CBV-2U4-3T(-N) points
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
67
M
AN0
13
9
re
v
14
327
No
SysMode (A327)
Enumerated value for System Mode
state:
0 = DB
1 = Heat
2 = Cool
0
no-units
0
no-units
334
Yes
netOCC (A334)
Enumerated value for Aspect
Schedule Point netOCC:
0 = Vacant
1 = Warmup
2 = Occupied
3 = Setback
2
no-units
2
no-units
369
Yes
TriStateHtVlvMinOnTime (A369)
Tristate valve minimum on time in
seconds
2 sec
2
sec
371
Yes
DegreesAbvBlwSPAlarm (A371)
Zone temperature error from current
temperature setpoints alarm
2 °F
2
°C
373
Yes
TempAlarmOnDelay (A373)
Amount of minutes before zone
temperature alarms are triggered
60 min
60
min
379
Yes
CFMAlarmOnDelay (A379)
Amount of minutes before Flowrate
alarms are triggered
30 min
30
min
380
Yes
TABParallelDisableFanSP (A380)
Parallel fan is enabled when Flowrate
is below this setpoint
3000 cfm
1500
l/sec
381
Yes
TABParallelFanDB (A381)
Parallel fan will be disabled when
Flowrate is above this point +
TABParallelDisableFanSP (A380)
50 cfm
25
l/sec
383
Yes
SeriesFanStartLckOutSP (A383)
Series fan is disabled if Flowrate is
above this setpoint when first
energized. If this occurs, damper will
drive shut and when Flowrate drops
below this setpoint series fan will
start
200 cfm
100
l/sec
385
Yes
SliderValAt_N2 (A385)
Resistance at
when slider is all
the way to the left
15 ohms
15
ohms
386
Yes
SliderValAt_N1 (A386)
Resistance at
when slider is
between all the way to left and
middle
1315 ohms
1315
ohms
387
Yes
SliderValAt_0 (A387)
Resistance at
when slider is in
middle
2800 ohms
2800
ohms
388
Yes
SliderValAt_P1 (A388)
Resistance at
when slider is
between all the way to right and
middle
4460 ohms
4460
ohms
389
Yes
SliderValAt_P2 (A389)
Resistance at
when slider is all
the way to the right
4989 ohms
4989
ohms