C1300
Advanced circular chart recorder
3 Configuration
IM/C1300 Rev. J
45
3.10 Analog Output Configuration
Overview.
Fitted analog outputs
– assignable to retransmit any process variable
Selectable analog output range
– allows maximum resolution on range of interest
Adjustable output range
– for non-standard and reversed outputs
The example below shows analog output 1 programmed to retransmit part of process variable 1's engineering range (250 to 750°C)
as a 4.0 to 20.0 mA current output.
4.0mA
(Output Range Low)
20.0mA
(Output Range High)
1000°C
(Engineering Range High)
Select Output
Source
Setting Output Ranges
PV1
PV2
PV3
PV4
0°C
(Engineering Range Low)
Range to be
transmitted
750°C
(Analog Output Range High)
250°C
(Analog Output Range Low)
Select Analog
Output
Position 1
Positiont 6
Analog Output Configuration
Press the
key to open the
Main Menu
.
Highlight
Analog Output
.
Select Analog Output
Select the analog output to be configured.
Analog Output Source
Select the source for the analog output.
Refer to Appendix A on page 77 for a description of sources.
Continued on next page.
Select Output
Analog Output 1
Alarms
Totalizers
Relays
Digital I/O
Analog Output
Modbus
Math Blocks
Logic Equations
O/P1 Source
Pen 1
None
O/P1 Range High
010.00 mV