Fault Elimination
Diagnosis
Cause/Remedy
Presence Detector
- The movements of the person are too slight
switches off although
- Increase switch-off delay on the "Time" potentiometer
someone is moving in
the detection zone:
Change on all three
- The values have been set via the ETS; via the Registration
potentiometers is not
Card "Settings" in each case, instead of "ETS", activate
accepted:
the setting option "Poti"
The Presence Detector as Constant Light Controller
Diagnosis
Cause/Remedy
Presence Detector
does not switch on:
- Percentage of daylight too high; adjust switching threshold
Presence Detector
does not control to the
desired brightness value: - No current reference value stored; set reference value