ABB BALDOR BC155 Installation & Operating Manual Download Page 11

2-5

MN705

Notes:

1. Excessive IR compensation will cause unstable operation and cogging.
2. If using tachometer feedback, the IR trimpot should be set to minimum, fully counterclockwise.

Current Limit Trimpot (CL)  

The CL trimpot sets the current limit, (overload), which limits the maximum current, (torque), to the 

motor. The CL trimpot is factory set to 1.5 times (150%) the full load rating. To increase the current 

limit value, rotate the CL trimpot clockwise. To decrease the current limit value, rotate the CL trimpot 

counterclockwise. Some applications may require a lower torque limit value to prevent damage to the 

process material or the driven equipment.

Caution:   Adjusting the CL above 150% of motor rating can cause overheating and possibly  demagnetization of 

some PM motors. Consult motor manufacturer.

To Recalibrate the CL trimpot:
1.  Disconnect the AC power and connect a DC ammeter in series with either motor armature lead.  

Observe correct polarity.

Note: An AC ammeter can be used by connecting it in series with either AC line input lead.

2.  Set the main speed potentiometer to approximately 30 – 50% clockwise position.
3.  Load the motor shaft in accordance with application requirements.
4.  Set the CL trimpot fully counterclockwise. Apply AC input power. The red CL LED will illuminate.
5.  While observing the ammeter, rotate the CL trimpot clockwise until the desired current, (torque), 

value is obtained. If using an AC ammeter the measured current value will be approximately 75% 

of the DC current value.

Note: On cyclical loads, it may be normal for the CL LED to momentarily flash.

Troubleshooting

Table  2-3 Troubleshooting Guide

Indication / Symptom

Possible Cause / Solution

Motor does not run.

AC input voltage not present at L1, L2 terminals. Verify correct wiring.
Blown line fuse or tripped circuit breaker. Blown armature fuse or control 

circuit fuse. Replace blown fuse with SL-40 or equivalent. If fuse blew due 

to miswiring, power bridge module may be defective.

Motor is not running. Power ON LED 

is illuminated.

Check ENABLE or INHIBIT circuit for loose or disconnected wiring.
Main speed pot is set to zero. Re-adjust to desired speed.
Main speed pot, speed reference signal input, or motor connections are 

open. Verify there are no loose or disconnected wires.

Motor hums or runs at very low speed. 

Motor slows when load is applied. CL 

LED is illuminated.

Incorrect motor wiring. Verify correct wiring.
Motor is overloaded. Check motor current with DC ammeter. Reduce load.
Motor may be defective. Check motor for shorts or grounds. Check brushes.
Current  Limit  (CL) trimpot  may not be set correctly.  Re-adjust  CL trimpot  

in accordance with section 5.2.6.

Motor runs at high speed and does not 

respond to main speed pot or speed 

reference signal.

Check field wiring. If using tachometer feedback, check tachometer signal.

Summary of Contents for BALDOR BC155

Page 1: ...6 15 Installation Operating Manual MN702 DC SCR Drives for BC155...

Page 2: ...Any trademarks used in this manual are the property of their respective owners Important Be sure to check www baldor com to download the latest version of this manual in Adobe Acrobat PDF format...

Page 3: ...onnection 2 2 Field Connection 2 2 Control Circuit Wiring 2 2 Speed Potentiometer Connection 2 2 Enable 2 2 Inhibit 2 2 DC Tachometer Connection 2 2 Armature Switching Dynamic Braking 2 3 Start up and...

Page 4: ...ii MN702...

Page 5: ...k can cause serious or fatal injury WARNING Electrical shock can cause serious or fatal injury Be sure that all power is disconnected and there is no voltage present from this equipment or equipment t...

Page 6: ...imum speed above the rated motor RPM since unstable motor operation may occur Receiving Each control is thoroughly tested at the factory and carefully packaged for shipment When you receive your contr...

Page 7: ...is 40 C 104 F The WATTS LOSS value of the control at full load is 60 watts Electrical Connections Connection terminals are shown in Figure 2 1 Figure 2 1 Connection Diagrams AC Line 50 60 Hz Armature...

Page 8: ...d the drive and motor will start and run when AC power is applied when power is restored after a momentary power loss or after an overload or TCL fault is reset The user must ensure that automatic sta...

Page 9: ...If a 20 Volts 1000 RPM tachometer is used with a 3600 RPM motor RT 1 3 X 20 X 3600 16000 77600 Ohms Choose the closest standard watt resistor value which in this case would be 75000 Ohms 75 K ARMATUR...

Page 10: ...crease the maximum speed rotate the MAX trimpot clockwise To decrease the maximum speed rotate the MAX trimpot counterclockwise Note The MAX trimpot is inoperative in the voltage following mode Cautio...

Page 11: ...he ammeter rotate the CL trimpot clockwise until the desired current torque value is obtained If using an AC ammeter the measured current value will be approximately 75 of the DC current value Note On...

Page 12: ...2 6 MN705...

Page 13: ......

Page 14: ......

Page 15: ...SUITE 400 ROGERS MN 55374 PHONE 763 428 3633 FAX 763 428 4551 MISSOURI ST LOUIS 13678 LAKEFRONT DRIVE EARTH CITY MO 63045 PHONE 314 373 3032 FAX 314 373 3038 KANSAS CITY 9810 INDUSTRIAL BLVD LENEXA KS...

Page 16: ...P O Box 2400 Fort Smith AR 72902 2400 U S A Ph 1 479 646 4711 Fax 1 479 648 5792 International Fax 1 479 648 5895 www baldor com Baldor Electric Company MN702 All Rights Reserved Printed in USA A4022...

Reviews: