CO NFIGURATIO N
VIEW DEVICES
4JNO0 0030 8 A
39
Table 13: Device Information
Field
Description
Device ID
The identification number assigned to the attached WirelessHART and
HART devices. It can be changed by using the “Edit Slave IDs” option on
the same page. See Section
for details.
Device Tag
Long tag of the HART device.
MAC Address
Displays the network card address for the corresponding WirelessHART
device.
Status
Displays whether a device is connected or disconnected.
PV
Displays the Primary Value of the corresponding HART device.
SV
Displays the Secondary Value of the corresponding HART device.
TV
Displays the Tertiary Value of the corresponding HART device.
QV
Displays the Quaternary
Value of the corresponding HART device.
Battery Life
Displays the expected remaining life of the battery powering the devices
(if “65535” is displayed, the device is line powered with a power supply or
waiting for battery life information to be provided by the device).
Neighbors
The number of neighbors a WirelessHART device can communicate with.
Timestamp
In (hh:mm) format, is the time when the data was most recently polled.
Latency
Measure of time it takes to respond and update all the corresponding
data fields (measured in seconds).
Bandwidth
In (msec/packet) format, is the available data rate to the corresponding
device.
Joins
The number of times a device connected to the gateway since bootup.
Command 3 period
HART command 3 continuous burst period.
Command 3 status
HART command 3 burst status (ON/OFF).
Active Pipe
This field shows the status of pipe for a device.
Note
: The Active Pipe option is available in firmware version 1.5-1.
Fast Pipe Control
Fast pipe can be enabled and disable for a device using this function.
Notes:
Only one device can have a pipe at any point in time.
The Fast Pipe Control option is available in firmware version 1.5-1.
6.7.1
Delete a Device
To remove a device from the list (i.e. WirelessHART network), right-click on the disconnected
device in
Devices
page and a delete option will appear. Select this option to confirm.
Only devices that are not connected may be deleted from the device list.
To delete an active device, power down the device and wait until the status col-
umn indicates the device is disconnected and the row is red.
Summary of Contents for AWIN GW120
Page 1: ... ENERGY INDUSTRIES ABB Wireless Industrial Network AWIN GW120 User Manual ...
Page 2: ......
Page 3: ... ENERGY INDUSTRIES ABB Wireless Industrial Network AWIN GW120 User Manual ...
Page 8: ......
Page 10: ......
Page 12: ......
Page 74: ......
Page 75: ......
Page 76: ... Visit us abb com awin Document Number 4JNO000308 Rev A ...