4 Electrical Installation
OI/FEA100/200–EN Rev. D
21
4.2 Environmental Protection
4.3 Sensor Terminal Box Connections – AquaMaster3 FET200 Transmitter
With AquaMaster3 FET2 transmitter the sensor terminal box is factory-wired, potted and terminated with a
plug for easy connection at the transmitter.
Fig. 4.2 Potting the Terminal Box – WaterMaster FET1 Transmitter
Warning.
Potting materials are toxic – use suitable safety precautions.
Read the manufacturers instructions carefully before preparing the potting material.
The remote sensor terminal box connections must be potted immediately on completion to
prevent the ingress of moisture.
Check all connections before potting – see Section 4, Page 20.
Do not overfill or allow the potting material to come into contact with 'O' rings or grooves.
Do not let potting material enter conduit, if used.