Operation principle
8
Graphs illustrating the effect of the du/dt filter
The graphs show the peak line-to-line voltage (
Û
LL
) and voltage change (du/dt) at
the motor terminals as a function of the motor cable length.
Û
LL
and du/dt are scaled
to the nominal line-to-line voltage (
U
N
). To calculate the actual peak voltage value in
volts and du/dt value in volts per microsecond, multiply the values of the graph by
the supply voltage (
U
N
).
The values in the first graph are measured with an ABB du/dt filter while the second
graph without any output filtering. The values in the second graph are only
representative. The actual unfiltered du/dt values depend on the drive type, and are
usually in the range of 1 to 5 kV/microsecond.
In case of drives with an IGBT supply unit or resistor braking, the
Û
LL
and du/dt
values are approximately 20% higher.
The voltage rise time can be calculated as follows: t = 0.8 ·
Û
LL
/(du/dt).
Û
LL
/
U
N
Without du/dt Filter
Cable length (m)
du/dt
U
N
-------------(1/
μ
s)
1.0
2.0
5.0
4.0
3.0
1.5
2.5
3.5
4.5
100
200
300
100
200
300
0.0
0.5
1.0
1.5
2.0
2.5
3.0
Cable length (m)
With du/dt Filter
du/dt
U
N
-------------(1/
μ
s)
Û
LL
/
U
N
5.5
Summary of Contents for AOCH0260-70
Page 2: ...3AFE58933368 REV G EN EFFECTIVE 2009 09 15 2009 ABB Oy All Rights Reserved ...
Page 6: ...About this manual 6 ...
Page 14: ...Installation 14 Power connection diagrams NOCH0260 60 NOCH0400 60 NOCH0760 60 NOCH0400 60 ...
Page 16: ...Installation 16 NOCH0760 60 ...
Page 17: ...Installation 17 NOCH0400 60 ...
Page 18: ...Installation 18 NOCH0400 60 ...
Page 19: ...Installation 19 AOCH0400 70 AOCH0260 70 ...
Page 27: ...Dimension drawings 27 NOCH0120 60 NOCH0260 60 and NOCH0400 60 du dt kits include 3 filters ...
Page 29: ...Dimension drawings 29 ...