42
1VAL050601-MB Rev C
APPENDIX C
I1002
I1004
KM1005 (INPUTS)
14 - Under voltage
13 + Under Voltage
12 - Close Blocking
11 + Close Blocking
10 Not Used
9 Not Used
8 - 2nd Trip/Protect trip
7 + 2nd Trip/Protect trip
6 - Aux Open/Safe Open
5 + Aux Open/Safe Open
4 - CB Remote Open
3 + CB Remote Open
2 - CB Remote Close
1 + CB Remote Close
KM1004 (OUTPUTS)
14 - Remote Open
13 + Remote Open
12 - Not Ready
11 + Not Ready
10 + Ready
9 - Ready
8 - CB Aux Closed
7 + CB Aux Closed
6 - CB Aux Open
5 + CB Aux Open
4 - CB Closed
3 + CB Closed
2 - CB Open
1 + CB Open
ED2.0 CIRCUIT BOARD CONNECTIONS, JUMPERS AND DIP SETTINGS
F IGURE 3 – ED2.0 CIRCUIT BOARD
KM10
02
12 Of
f C
o
il
11 Of
f C
o
il
10 On Coil
9 On Coil
8 Off C
o
il
7 Off C
o
il
6 On
Coil
5 On
Coil
4 GN
D
3 GN
D
2 80V
1 80V
KM10
03
6
5 cap d
ischar
g
e
4 cap d
ischar
g
e
3 -
A
u
x Sup
p
ly
2 +
A
u
x Su
ppl
y
1 GN
D
KM10
01 POSITION
SENSORS
CB Open SI
G +
18 VDC 6
CB Clo
sed SI
G
+18 VDC 5
+18 VDC 4
+18 VDC 3
0 VDC 2
0 VDC 1
KM1007
PUSH BUTTON ASSY
JP1001
PROTECTION TRIP / SECOND TRIP
NORMAL
PROTECTION
NOTE: The filter card has wire
jumpers for each binary input.
If the jumpers are left in-
stalled, the input voltage
threshold is as listed in the
instruction book. If cut the
voltage level required is ap-
proximately 20V higher.
These are typically “not al-
ways” cut for high voltage
board applications and are left
intact for low voltage boards.
I1002 AUX/SAFE OPEN and UV BLOCK OPEN
JP1019
ADD JUMPER FOR
LOW POWER 33 WATT SET-
TING
I1001
Provided
by
Northeast
Power
Systems,
Inc.
(NEPSI)
Summary of Contents for AMVAC
Page 2: ...2 1VAL050601 MB Rev C Provided by Northeast Power Systems Inc NEPSI ...
Page 46: ...46 1VAL050601 MB Rev C APPENDIX F Provided by Northeast Power Systems Inc NEPSI ...
Page 47: ...47 1VAL050601 MB Rev C APPENDIX G Provided by Northeast Power Systems Inc NEPSI ...
Page 49: ...49 1VAL050601 MB Rev C NOTES Provided by Northeast Power Systems Inc NEPSI ...