Quick installation guide - ACSM1-04
4
it is however highly recommended to fasten
these modules to the mounting base also by
two screws through the lower mounting holes.
For installation of the cold plate drive modules
(ACSM1-04Cx-xxxx-x), follow the instructions
in the
ACSM1-04 Drive Modules (0.75 to 45
kW) Hardware Manual.
Electrical installation
*Note:
For motor cabling, use a separate
ground cable if the conductivity of the motor
cable shield is less than 50% of that of a phase
conductor and the cable has no symmetrical
ground conductors.
Power cabling procedure
Cabling examples are presented on page
.
Tightening torques are presented on page
and at appropriate points in the text.
• Attach the terminal blocks included to the
drive.
• ACSM1-04xx-
024A
…
090A
-4 only: Remove
the two plastic connector covers at the top
and bottom of the drive. Each cover is held
by two screws.
• On IT (ungrounded) systems and corner-
grounded TN systems, remove the screw
labelled VAR located close to the supply
terminals.
• Fasten the two cable clamp plates included
to the drive, one at the top, one at the
bottom. The clamp plates are identical.
• Strip the power cables so that the shields are
bare at the cable clamps.
• Connect the supply, resistor (if present) and
motor cables to the appropriate terminals of
the drive.
• Tighten the cable clamps onto the bare cable
shields. Connect the ends of the cable
shields to the ground terminals using cable
lugs. Cover visible bare shield with insulating
tape.
• ACSM1-04xx-
024A
…
090A
-4 only: Cut
suitable slots on the edges of the connector
covers to accommodate the cables. Refit the
covers.
• Ground the motor cable shield at the motor
end.
PE
*
PE
Braking resistor
(optional)
L1 L2 L3
UDC+ UDC–
R– R+
U2 V2 W2
U1 V1 W1
3~
Motor
V1
W1
U1
ACSM1-04
PE
U
V
W
PE
X
Y
Z
L1
L2
L3
L1’
L2’
L3’
Supply disconnecting
device (disconnecting
means) with fuses
CHK-xx mains choke
(optional)
JFI-xx mains filter
(optional)
ACSM1-04xx-02A5…016A-4:
1.5 N·m (13 lbf·in)
ACSM1-04xx-024A…090A-4:
3 N·m (25 lbf·in)
1.5 N·m
(13 lbf·in)