516 Fault tracing
A981
External warning 1
(Editable message text)
Programmable warning:
Fault in external device 1.
Check the external device.
Check setting of parameter
.
A982
External warning 2
(Editable message text)
Programmable warning:
Fault in external device 2.
Check the external device.
Check setting of parameter
.
A983
External warning 3
(Editable message text)
Programmable warning:
Fault in external device 3.
Check the external device.
Check setting of parameter
.
A984
External warning 4
(Editable message text)
Programmable warning:
Fault in external device 4.
Check the external device.
Check setting of parameter
.
A985
External warning 5
(Editable message text)
Programmable warning:
Fault in external device 5.
Check the external device.
Check setting of parameter
.
AF80
INU-LSU comm loss
Programmable warning:
DDCS (fiber optic)
communication between
converters (for example, the
inverter unit and the supply
unit) is lost.
Note that the inverter unit will
continue operating based on
the status information that was
last received from the other
converter.
Check status of other converter
(parameters
and
).
Check settings of parameter group
. Check the
corresponding settings in the control
program of the other converter.
Check cable connections. If necessary,
replace cables.
AF85
Line side unit warning
The supply unit (or other
converter) has generated a
warning.
The auxiliary code specifies the original
warning code in the supply unit control
program. See section
(page
).
AF8C Process PID sleep
mode
The drive is entering sleep
mode.
Informative warning. See section
function for process PID control
(page
), and parameters
AF90
Speed controller
autotuning
The speed controller autotune
routine did not complete
successfully.
Check the auxiliary code (format XXXX
YYYY). “YYYY” indicates the problem
(see actions for each code below).
0000 The drive was stopped before
the autotune routine finished.
Repeat autotune until successful.
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...