138 Parameters
Selects a binary source whose status is transmitted as bit 13
of
.
False
0.
0
True
1.
1
). -
Selects a binary source whose status is transmitted as bit 14
of
.
False
0.
0
True
1.
1
). -
(Only visible when supply unit control activated by
Shows the status of the supply unit.
See also section
Control of a supply unit (LSU)
(page
), and
parameter group
This parameter is read-only.
-
0000h…FFFFh
Supply unit status word.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Ready on
1 = Ready to switch on
1
Ready run
1 = Ready to operate, DC link charged
2
Ready ref
1 = Operation enabled
3
Tripped
1 = A fault is active
4…6
Reserved
7
Warning
1 = A warning is active
8
Modulating
1 = The supply unit is modulating
9
Remote
1 = Remote control (EXT1 or EXT2)
0 = Local control
10
Net ok
1 = Supply network voltage OK
11
User bit 0
Selectable in supply control program
12
User bit 1
Selectable in supply control program
13
User bit 2
Selectable in supply control program
14
Charging
1 = Charging circuit active
0 = Charging circuit inactive
15
User bit 3
Selectable in supply control program
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...