338 Parameters
Defines the “at setpoint” limits for torque control of the drive.
When the absolute difference between reference (
) and actual torque (
, the drive is
considered to be “at setpoint”. This is indicated by bit 8 of
.
10.0%
0.0 … 300.0%
Limit for “at setpoint” indication in torque control.
See par.
Defines the trigger level for “above limit” indication in speed
control. When actual speed exceeds the limit, bit 10 of
is set.
1500.00 rpm
0.00 … 30000.00
rpm
“Above limit” indication trigger level for speed control.
See par.
Defines the trigger level for “above limit” indication in
frequency control. When actual frequency exceeds the limit,
bit 10 of
is set.
50.00 Hz
0.00 … 1000.00 Hz
“Above limit” indication trigger level for frequency control.
See par.
Defines the trigger level for “above limit” indication in torque
control. When actual torque exceeds the limit, bit 10 of
is set.
300.0%
0.0 … 1600.0%
“Above limit” indication trigger level for torque control.
See par.
Defines the number of decimal places of torque-related
parameters.
1
0…2
Number of decimal places of torque parameters.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
(%)
0 %
+
(%)
(%)
-
(%)
Drive at setpoint
bit 8 = 1)
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...