![ABB ACS880 Series Electrical Planning Manual Download Page 17](http://html1.mh-extra.com/html/abb/acs880-series/acs880-series_electrical-planning-manual_3381105017.webp)
■
Multidrive modules
IGBT supply modules ACS880-204LC
See the instructions given for the cabinet-installed multidrives.
Diode supply modules ACS880-304LC+A019
The supply modules do not have input chokes. For this reason, dimension the supply
transformer according to the supply unit apparent power (
S
n
), and make sure that the supply
transformer impedance is suitable for the supply unit. The transformer reactance
X
k
has to
be at least 4% and the transformer nominal apparent power (
S
n
) must not be more than 2
times the nominal apparent power (
S
n
) of the supply unit in question.
Electrical planning guidelines 17