118 Technical data
Supply cable fuses
Fuses for short circuit protection of the supply cable are listed below. The fuses also
protect the adjoining equipment of the drive in case of a short circuit.
Check that the operating time of the fuse is below 0.5 seconds. The operating time
depends on the supply network impedance and the cross-sectional area and length
of the supply cable. See also chapter
Planning the electrical installation
on page
Note:
Fuses with a higher current rating must not be used.
Drive type
ACS880-M04
Input
current
(A)
IEC fuse
UL fuse
Cross-sectional
area of cable
Rated
current
(A)
Volt-
age
(V)
Class Rated
current
(A)
Volt-
age
(V)
UL
class
mm
2
AWG
-03A0-2, -03A0-5 4.0*
6
500
gG
6
600
T
1.5…4
16…12
-03A6-2, -03A6-5 6.0*
6
500
gG
6
600
T
1.5…4
16…12
-04A8-2, -04A8-5 7.0*
10
500
gG
10
600
T
1.5…4
16…12
-06A0-2, -06A0-5 9.0*
10
500
gG
10
600
T
1.5…4
16…12
-08A0-2, -08A0-5 11*
16
500
gG
15
600
T
1.5…4
16…12
-010A-2, -010A-5 13*
16
500
gG
15
600
T
1.5…10 16…8
-014A-2, -014A-5 18*
20
500
gG
20
600
T
1.5… 0 16…8
-018A-2, -018A-5 23*
25
500
gG
25
600
T
1.5…10 16…8
-025A-2, -025A-5 20
25
500
gG
25
600
T
6…35
9…2
-030A-2, -030A-5 26
32
500
gG
35
600
T
6…35
9…2
-035A-2, -035A-5 30
40
500
gG
35
600
T
6…35
9…2
-044A-2, -044A-5 36
50
500
gG
45
600
T
6…35
9…2
-050A-2, -050A-5 42
50
500
gG
50
600
T
10…70 6…2/0
-061A-2, -061A-5 55
63
500
gG
70
600
T
10…70 6…2/0
-078A-2, -078A-5 65
80
500
gG
80
600
T
10…70 6…2/0
-094A-2, -094A-5 82
100
500
gG
100
600
T
10…70 6…2/0
*Without mains choke
AWG cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) surrounding air temperature. Not more than three current-carrying conductors in raceway or cable
or earth (directly burried). For other conditions, dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
Summary of Contents for ACS880-M04
Page 1: ...ABB machinery drives Hardware manual ACS880 M04 drive ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Safety instructions ...
Page 28: ...28 About the manual ...
Page 38: ...38 Operation principle and hardware description ...
Page 48: ...48 Planning the cabinet installation ...
Page 54: ...54 Mechanical installation ...
Page 72: ...72 Planning the electrical installation ...
Page 98: ...98 Electrical installation ...
Page 102: ...102 Start up ...
Page 108: ...108 Maintenance ...
Page 140: ...140 Technical data ...
Page 158: ...158 Mains chokes ...
Page 164: ...164 EMC filters 7 Attach the terminal blocks to the filter 1 6 5 4 3 ...
Page 166: ...166 EMC filters 6 Attach the terminal blocks to the filter 1 2 3 4 ...
Page 168: ...168 EMC filters ...
Page 182: ...Dimension drawings 182 Frame size R1 H1 H2 W D ...
Page 183: ...Dimension drawings 183 Frame size R2 H2 H1 W D ...
Page 184: ...Dimension drawings 184 Frame size R3 D W H1 H2 ...
Page 185: ...Dimension drawings 185 Frame size R4 W H1 H2 D ...
Page 187: ...187 Dimension drawings EMC filters type JFI x1 JFI A1 ...
Page 188: ...Dimension drawings 188 JFI B1 ...
Page 189: ...189 Dimension drawings EMC filters type JFI 0x ...
Page 191: ...191 Dimension drawings Brake resistors type JBR xx ...
Page 193: ...193 Dimension drawings ...
Page 195: ...www abb com drives www abb com drivespartners 3AXD50000028613 Rev A EN 2016 04 11 Contact us ...