Parameters 341
Specifies hardware-related options that require
differentiated parameter defaults. Activating a bit in this
parameter makes the necessary changes in other
parameters – for example, activating an emergency stop
option reserves a digital input. In most cases, the
differentiated parameters will also be write-protected.
This parameter, as well as the changes in other
parameters implemented by it, are not affected by a
parameter restore.
-
0000h…FFFFh
Hardware options configuration word 1.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Information
0
Supply frequency 60 Hz
0 = 50 Hz; 1 = 60 Hz. Affects parameters
,
,
,
,
1
Emergency stop Cat 0
Emergency stop, Category 0, without FSO module.
Affects parameters
,
,
.
2
Emergency stop Cat 1
Emergency stop, Category 1, without FSO module.
Affects parameters
,
,
3
RO2 for -07 cabinet cooling
fan
1 = Control of cabinet cooling fan (used only with
specific ACS880-07 hardware). Affects parameters
4
Externally powered control
unit
1 = Control unit powered externally. Affects parameter
5
DC supply switch
1 = DC switch monitoring active. Affects parameters
Note:
Setting this bit activates the Run enable signal.
Recheck
and adjust if necessary
6
DOL motor switch
1 = Motor fan control active. Affects parameters
.
7
xSFC-01 fuse switch
controller
1 = xSFC charging controller used. Affects parameter
8
Service switch
1 = Service switch connected. Affects parameters
,
9
Output contactor
1 = Output contactor present. Affects parameters
10
Brake resistor, sine filter,
IP54 fan
1 = Status (eg. thermal) switches connected to DIIL
input. Affects
,
.
11
INU-DSU communication
Supply unit control by inverter unit.
1 = Yes (activates communication through RDCO
module CH1)
12
Reserved
13
Du/dt filter activation
1 = A du/dt filter is connected to the drive/inverter output.
Note:
This bit is to be left at 0 if the drive/inverter module
is equipped with internal du/dt filtering (for example,
frame R8i inverter modules with E205).
14
DOL fan activation
Reserved
15
INU-ISU communication
1 = IGBT supply unit control by inverter unit active.
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...