Parameters 143
Defines the real internal value that corresponds to the
minimum analog input AI1 value defined by parameter
. (Changing the polarity settings of
and
can effectively invert the analog input.)
0.000
-32768.000
…32767.000
Real value corresponding to minimum AI1 value.
1 = 1
Defines the real internal value that corresponds to the
maximum analog input AI1 value defined by parameter
. See the drawing at parameter
.
1500.000;
1800.000
(
-32768.000
…32767.000
Real value corresponding to maximum AI1 value.
1 = 1
Displays the value of analog input AI2 in mA or V
(depending on whether the input is set to current or voltage
by a hardware setting).
This parameter is read-only.
-
-22.000
…22.000 mA or V
Value of analog input AI2.
1000 = 1 mA
or V
Displays the value of analog input AI2 after scaling. See
parameters
.
This parameter is read-only.
-
-32768.000
…32767.000
Scaled value of analog input AI2.
1 = 1
Selects the unit for readings and settings related to analog
input AI2.
Note: This setting must match the corresponding hardware
setting on the drive control unit (see the hardware manual
of the drive). Control board reboot (either by cycling the
power or through parameter
) is
required to validate any changes in the hardware settings.
V
Volts.
2
mA
Milliamperes.
10
No.
Name/Value
Description
Def/
FbEq16
AI
in
(
AI
scaled
(
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...