Parameters 155
(Visible when
Defines the activation delay for digital input/output DIO3.
0.0 s
t
On
t
Off
*Electrical status of DIO (in input mode) or status of selected source (in output mode). Indicated by
.
.
0.0…3000.0 s
Activation delay for DIO3.
10 = 1 s
(Visible when
The true readings of the analog inputs can be overridden
for eg. testing purposes. A forced value parameter is
provided for each analog input, and its value is applied
whenever the corresponding bit in this parameter is 1.
0000b
0000b …0111b
Forced values selector for analog inputs.
1 = 1
(Visible when
Defines the deactivation delay for digital input/output
DIO3. See parameter
0.0 s
0.0…3000.0 s
Deactivation delay for DIO3.
10 = 1 s
(Visible when
Selects whether DIO4 of the extension module is used as
a digital input or output.
Output
DIO4 is used as a digital output.
0
Input
DIO4 is used as a digital input.
1
(Visible when
Selects a drive signal to be connected to digital
input/output DIO4 when parameter
set to
.
For the available selections, see parameter
.
No.
Name/Value
Description
Def/
FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
*DIO status
**Delayed DIO
status
Time
Bit
Value
0
1 = Force AI1 to value of parameter
.
1
1 = Force AI2 to value of parameter
.
2
1 = Force AI3 to value of parameter
(FIO-11 only).
3…15
Reserved.
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...