Cross sections are typically 4×95 mm
2
, 4×120 mm
2
or 4×150 mm
2
.
Terminal [X350] data for the control cables
Terminal type: Spring-cage connection
Conductor stripping length: 8…10 mm
Conductor max. size: 4 mm
2
(solid), 2.5 mm
2
(stranded)
Conductor min. size: 0.08 mm
2
(solid), 0.08 mm
2
(stranded, no ferrule), 0.14 mm
2
(stranded,
with ferrule)
DC connection data
See
Selecting the energy storage (page 24)
Auxiliary circuit current consumption
Auxiliary circuit current consumption varies depending on the actual drive configuration and
options. Contact ABB for the delivery-specific value.
Energy efficiency data (ecodesign)
Energy efficiency data is not provided for the drive/unit. The multidrives are not in the scope
of the EU ecodesign requirements (Regulation EU/2019/1781) or the UK ecodesign
requirements (Regulation SI 2021 No. 745).
Protection classes
IP42 (standard), IP54 (B055)
Degrees of protection
(IEC/EN 60529)
UL Type 1 (standard), UL Type 12 (B055). For indoor use only.
Enclosure types (UL50)
III, except for auxiliary power connections (fan, control, heating, lighting, cooling
unit pump etc) which are category II.
Overvoltage category
(IEC/EN 60664-1)
I
Protective class
(IEC/EN 61800-5-1)
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Transportation
in the protective package
Storage
in the protective package
Operation
installed for stationary
use
-
-
0…2000 m (0…6562 ft)
above sea level. For alti-
tudes over 2000 m, contact
ABB.
Installation site altitude
Output derated above 1000
m (3281 ft).
Technical data 57
Summary of Contents for ACS880-7107LC DC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 7107LC DC feeder unit Hardware manual ...
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 ...
Page 22: ...22 ...
Page 36: ...36 ...
Page 40: ...40 ...
Page 44: ...44 ...
Page 50: ...50 ...
Page 52: ...52 ...
Page 55: ...Terminal and cable entry data for the power cables Technical data 55 ...