Start-up and acceptance test 47
Push the emergency stop reset button [S62].
• Make sure that
the indication lamp goes [P62] off.
• Make sure that the drive does not restart automatically at this point.
Switch off the drive start signal (only in external control mode).
If the drive generates a fault message, reset the drive.
Restart the drive and motor and check that they operate normally.
Repeat the test from each operating location (every emergency stop button and reset button).
Fill in and sign the acceptance test report which verifies that the safety function is safe and accepted
to operation.