background image

EN – Quick installation guide   3

EN

DA

DE

ES

FI

FR

IT

PL

PT

RU

SV

TR

ZH

EN – Quick installation guide

Contents of this guide

This guide tells you briefly how to install the drive module into a 800 mm wide Rittal TS 8 
cabinet. For installation examples in different cabinets and more detailed instructions, 
engineering guide lines, technical data and complete safety instructions, see the hardware 
manual (

www.abb.com/drives

: Select 

Document Library

 and search for document number 

3AXD50000035160 [English]).

Obey the safety instructions

See figures on page 

9

. If you ignore these instructions, injury or death, or damage to the 

equipment can occur.

WARNING! 

Handle the drive module carefully. Open the support legs by pressing 

each leg a little down and turning it aside (1, 2).

Do not tilt the drive module.

 

It is 

heavy

 and its

 center of gravity is high.

 The 

module will overturn from a sideways tilt of 5 degrees. Do not leave the module 
unattended on a sloping floor. 

To prevent the drive module from falling, attach its top lifting lugs with chains to the cabinet 
frame before you push the module into the cabinet. Work carefully preferably with help 
from another person. Keep a constant pressure with one foot on the base of the module to 
prevent the module from falling on its back.

WARNING! 

If you are not a qualified electrical professional, do not do installation 

or maintenance work. Go through these steps before you begin any installation or 
maintenance work.

1. Clearly identify the work location. 

2. Disconnect all possible voltage sources. 

Open the main disconnector of the drive.

Open the disconnector of the supply transformer as the main disconnector of the 
drive does not remove the voltage from the input busbars of the drive.

Make sure that reconnection is not possible. Lock the disconnectors to open 
position and attach a warning notice to them. 

Disconnect any external power sources from the control circuits before you do 
work on the control cables. 

After you disconnect the drive, always wait for 5 minutes to let the intermediate 
circuit capacitors discharge before you continue. 

3. Protect any other energized parts in the work location against contact.

4. Take special precautions when close to bare conductors.

Summary of Contents for ACS880-14

Page 1: ...ABB industrial drives Quick installation guide ACS880 14 drive modules 132 to 400 kW 200 to 450 hp English 3 EN ...

Page 2: ...ls user s manual 3AUA0000085685 Drive firmware manuals and guides ACS880 primary control program firmware manual 3AUA0000085967 Quick start up guide for ACS880 drives with primary control program 3AUA0000098062 ACS880 IGBT supply control program firmware manual 3AUA0000131562 Option manuals and guides DPMP 01 mounting platform for ACS AP control panel installation guide 3AUA0000100140 DPMP 02 03 m...

Page 3: ... top lifting lugs with chains to the cabinet frame before you push the module into the cabinet Work carefully preferably with help from another person Keep a constant pressure with one foot on the base of the module to prevent the module from falling on its back WARNING If you are not a qualified electrical professional do not do installation or maintenance work Go through these steps before you b...

Page 4: ...e drive without derating is 15 to 40 C Protect the drive and input power cables See table on page 9 Installing the drive module and LCL filter module into a cabinet See appendix Step by step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet Attach the plinth to the floor Attach the cabinet frame to the plinth Make the bottom plate with 360 degr...

Page 5: ...sure with one foot on the base of the module to prevent the module from falling on its back Unfasten the insertion ramp and attach the drive module to the bottom plate Attach the LCL filter module and drive module to the punched section Attach LCL filter module to the side of drive module from top and bottom Reinstall the cover Connect the LCL filter busbars to the drive module busbars with the co...

Page 6: ...les in the vertical direction according to the alignment holes in the shroud Smooth the hole edges Remove the plastic sheeting from both sides of the shroud Attach the cables firmly to the cabinet frame to prevent chafing against the hole edges 4 Put the conductors of the input cables through the drilled holes in the clear plastic shroud 5 For drive modules without option H370 Connect the input ca...

Page 7: ... Default I O connections The default I O connections of the Factory macro of the ACS880 primary control program are shown below Wire sizes and tightening torques of the control board terminals 0 5 2 5 mm2 24 14 AWG and 0 5 N m 4 lbf in for both stranded and solid wiring ...

Page 8: ... 1 Drive to drive link J3 XD2D Drive to drive link termination ON OFF Drive to drive link Shield 4 BGND 3 A 2 B 1 Safe torque off XSTO Safe torque off Both circuits must be closed for the drive to start IN2 4 IN1 3 SGND 2 OUT 1 Digital inputs XDI By default not in use DI6 6 Constant speed 1 select 1 on DI5 5 Acceleration deceleration select DI4 4 Reset DI3 3 Forward 0 Reverse 1 DI2 2 Stop 0 Start ...

Page 9: ... 2100 14200 170M6414 UN 500 V 240A 5 2100 5280 170M4410 260A 5 2100 6400 170M5408 302A 5 2100 8000 170M5410 361A 5 2100 8000 170M6410 414A 5 2100 10000 170M6411 460A 5 2100 12600 170M6411 503A 5 2100 14200 170M6412 UN 690 V 142A 7 2100 5280 170M4409 174A 7 2100 6400 170M4410 210A 7 2100 8000 170M5408 271A 7 2100 10000 170M5410 330A 7 2100 12600 170M6410 370A 7 2100 14200 170M6411 430A 7 2100 16000...

Page 10: ...Step by step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 360 Rittal TS 131 800 Rittal TS 8612 580 1752 5 69 00 Tapping screw M6 12 Torx T30 8 N m ...

Page 11: ...Step by step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 11 Combi screw M8 30 Hex 20 N m Tapping screw M6 12 Torx T30 Hex 8 N m ...

Page 12: ...by step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet Combi screw M4 8 Torx T20 2 N m Combi screw M4 8 Torx T20 2 N m Combi screw M4 8 Torx T20 2 N m 1 ...

Page 13: ...p drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 13 Combi screw M8 24 N m Combi screw M8 24 N m M6 Serpress 8 N m M6 Serpress 8 N m Screw M10 30 and washer ...

Page 14: ... drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet Combi screw M4 8 Torx T20 2 N m Combi screw M4 8 Torx T20 2 N m Combi screw M12 25 70 N m FAN3 LCL Screw M10 30 ...

Page 15: ...Step by step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 15 Combi screw M6 12 Torx T25 8 N m Combi screw M12 25 Hex Delta 70 N m 8 N m ...

Page 16: ...16 Step by step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet ...

Page 17: ...wings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 17 1 2 3 4 5 6 7 8 Combi screw M6 20 Torx T25 2 N m Combi screw M6 20 Torx T25 2 N m Combi screw M4 10 Torx T20 2 N m ...

Page 18: ...18 Step by step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 1 2 3 4 Hex screw M12 35 full thread 70 N m Hex nut M12 70 N m ...

Page 19: ...step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 19 Combi screw M4 10 Torx T20 2 N m Combi screw M4 10 Torx T20 2 N m Combi screw M6 20 Torx T25 2 N m ...

Page 20: ...20 Step by step drawings for an installation example of standard drive configuration in Rittal TS 8 800 mm wide cabinet 737 29 02 Tapping screw M6 12 Torx T30 Hex 8 N m ...

Page 21: ...ormation on ABB product training navigate to www abb com drives and select Training courses Providing feedback on ABB Drives manuals Your comments on our manuals are welcome Go to www abb com drives and select Document Library Manuals feedback form LV AC drives Document library on the Internet You can find manuals and other product documents in PDF format on the Internet Go to www abb com drives a...

Page 22: ...www abb com drives www abb com drivespartners 3AXD50000212446 Rev A MUL 2018 03 23 Contact us ...