M
3~
Size the fuses or circuit breakers according to local regulations for the input cable
protection. Select the fuses or circuit breakers for the drive according to the instructions
given in the technical data. The fuses for the drive protection will restrict drive damage
and prevent damage to adjoining equipment in case of a short-circuit inside the drive.
Note:
If the fuses or circuit breakers for the drive protection are placed at the distribution
board and the input cable is dimensioned according to the nominal input current of the
drive given in the technical data, the fuses or circuit breakers protect also the input cable
in short-circuit situations, restrict drive damage and prevent damage to adjoining
equipment in case of a short-circuit inside the drive. No separate fuses or circuit breakers
for the input cable protection are needed.
WARNING!
Due to the inherent operating principle and construction of circuit breakers,
independent of the manufacturer, hot ionized gases can escape from the breaker
enclosure in case of a short-circuit. To ensure safe use, pay special attention to
the installation and placement of the breakers. Obey the manufacturer’s
instructions.
■
Circuit breakers
See section
Circuit breakers (IEC) (page 177)
or
Circuit breakers (UL) (page 177)
.
■
Protecting the motor and motor cable in short-circuits
The drive protects the motor cable and motor in a short-circuit situation when the motor
cable is sized according to the nominal output current of the drive.
■
Protecting the motor cables against thermal overload
The drive protects the motor cables against thermal overload when the cables are sized
according to the nominal output current of the drive. No additional thermal protection
devices are needed.
WARNING!
If the drive is connected to multiple motors, use a separate overload protection
for each motor cable and motor. The drive overload protection is tuned for the
total motor load. It may not detect an overload in one motor circuit only.
Guidelines for planning the electrical installation 73
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...