UL fuses per drive module
Drive type
Fuse
Input current
(A)
Type
UL class
Manufacturer
V
A
U
n
= 480 V
JJS-600
T
Bussmann
600
600
459
ACS880-04F-459A-5
JJS-600
T
Bussmann
600
600
502
ACS880-04F-502A-5
A4BY800
L
Ferraz
600
800
582
ACS880-04F-582A-5
A4BY800
L
Ferraz
600
800
634
ACS880-04F-634A-5
A4BY1000
L
Ferraz
600
1000
715
ACS880-04F-715A-5
A4BY1000
L
Ferraz
600
1000
820
ACS880-04F-820A-5
A4BY1000
L
Ferraz
600
1000
880
ACS880-04F-880A-5
U
n
= 575 V
JJS-500
T
Bussmann
600
500
329
ACS880-04F-329A-7
JJS-500
T
Bussmann
600
500
369
ACS880-04F-369A-7
JJS-500
T
Bussmann
600
500
429
ACS880-04F-429A-7
JJS-600
T
Bussmann
600
600
470
ACS880-04F-470A-7
JJS-600
T
Bussmann
600
600
522
ACS880-04F-522A-7
A4BY800
L
Ferraz
600
800
590
ACS880-04F-590A-7
A4BY800
L
Ferraz
600
800
650
ACS880-04F-650A-7
A4BY800
L
Ferraz
600
800
721
ACS880-04F-721A-7
■
Notes for UL fuses
1.
Fuses are required as part of the installation, are not included in the base drive
configuration and must be provided by others.
2.
Fuses with a higher current rating than specified must not be used.
3.
The UL listed fuses recommended by ABB are the required branch circuit protection
per NEC.
4.
The recommended size or smaller UL listed 248 fast acting, time delay, or high
speed fuses must be used to maintain the UL listing of the drive. Additional
protection can be used. Refer to local codes and regulations.
5.
A fuse of a different class can be used at the high fault rating where the
I
peak
and
I
2
t of the new fuse is not greater than that of the specified fuse.
6.
UL listed 248 fast acting, time delay, or high speed fuses from other manufacturers
can be used if they meet the same class and rating requirements specified in the
rules above.
7.
When you install a drive, always obey ABB installation instructions, NEC
requirements and local codes.
8.
Alternative fuses can be used if they meet certain characteristics. For permitted
fuses, see
Branch Circuit Protection for ABB drives manual supplement