Fault tracing 569
Warning messages
Note:
The list also contains events that only appear in the Event log.
Code
(hex)
Warning
Cause
What to do
A2A1
Current calibration
Current offset and gain
measurement calibration will
occur at next start.
Informative warning. (See parameter
.)
A2B1
Overcurrent
Output current has exceeded
internal fault limit.
Check motor load.
Check acceleration times in parameter
group
(speed
control),
(frequency control). Also
,
Check motor and motor cable (including
phasing and delta/star connection).
Check there are no contactors opening
and closing in motor cable.
Check that the start-up data in parameter
group 99 corresponds to the motor rating
plate.
Check that there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check encoder cable (including
phasing).
Check the auxiliary code (format XXXY
YYZZ). With parallel-connected inverter
modules, “Y YY” specifies through which
BCU control unit channel the fault was
received. “ZZ” indicates the phase that
triggered the fault (
0:
No detailed
information available,
1:
U-phase,
2:
V-
phase,
4:
W-phase,
3
/
5/6/7:
multiple
phases).
A2B3
Earth leakage
Programmable fault:
Drive has detected load
unbalance typically due to
earth fault in motor or motor
cable.
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable.
Try running the motor in scalar control
mode if allowed. (See parameter
.)
If no earth fault can be detected, contact
your local ABB representative.
A2B4
Short circuit
Short-circuit in motor cable(s)
or motor.
Check motor and motor cable for cabling
errors.
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...