![ABB ACS880-01 Series Firmware Instructions Download Page 497](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621497.webp)
Parameters 497
Defines the nominal motor shaft torque. This value can be
given instead of nominal power (
) if shown on the rating
plate of the motor.
The unit is selected by parameter
.
Notes:
• This setting is an alternative to the nominal power value
(
). If both are entered,
takes priority.
• This parameter cannot be changed while the drive is
running.
0.000
N·m or lb·ft
0.000…
N·m or lb·ft
Nominal motor torque.
1 = 1 unit
Selects the type of the motor identification routine (ID run)
performed at the next start of the drive. During the ID run, the
drive will identify the characteristics of the motor for optimum
motor control.
If no ID run has been performed yet (or if default parameter
values have been restored using parameter
), this parameter is automatically set to
signifying that an ID run must be performed.
After the ID run, the drive stops and this parameter is
automatically set to
.
Notes:
• For
ID run, the machinery must always be
de-coupled from the motor.
• With a permanent magnet or synchronous reluctance
motor, a
or
ID run requires that
the motor shaft is NOT locked and the load torque is less
than 10%.
• With scalar control mode (
=
Current measurement calibration
ID run
mode is possible.Configure motor temperature
measurement (if used) in parameter group
before activating the ID run.
• If a sine filter is installed, set the appropriate bit in
before activating the
ID run. With a non-ABB (custom) filter, set also
.
• With scalar control mode (
=
), the ID run is not requested automatically. However,
an ID run can be performed for more accurate torque
estimation.
• Once the ID run is activated, it can be canceled by
stopping the drive.
• The ID run must be performed every time any of the motor
parameters (
) have been changed.
• Ensure that the Safe torque off and emergency stop
circuits (if any) are closed during the ID run.
• Mechanical brake (if present) is not opened by the logic for
the ID run.
• This parameter cannot be changed while the drive is
running.
b1/b2)
None
No motor ID run is requested. This mode can be selected
only if the ID run
(
,
)
has already been performed once.
0
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...