Parameters 435
Linear
Overload limit is calculating by formula:
T
act
= T
set
* (I
lim
/ I
act
)
Where,
T
act
T
set
I
lim
I
act
Quadratic
T
act
= T
set
* (I
lim
/ I
act
)
2
Where,
T
act
T
set
I
lim
I
act
Defines the time used as on-delay for the overload protection
function to react to the overload condition.
10.0
0.0...30000.0 s
Overload delay in seconds.
1 = 1s
Defines the response to the overload condition.
If the overload supervision signal is above active overload
limit in the defined delay time, then overload protection
function trigger the reaction defined in this parameter setting.
Not selected
Overload event reaction is inactive.
Warning
Overload condition triggers the drive event
warning. It will stay on as long as overload condition is
present. The warning will automatically disappear if overload
supervision signal stays below the overload limit for the time
defined in parameter
Warning with
shutdown
Overload condition triggers the drive event
warning and immediate stop command. Drive will stop
according to parameter
setting.
Fault
Overload condition triggers the drive event
fault which immediately trips the drive.
Recovery - Warning Overload condition triggers the overload recovery sequence.
In case recovery routine helps, the motor speed returns to
production speed. If not, drive generates the event
warning. It will stay on as long as overload condition
is present. The warning will automatically disappear if
overload supervision signal stays below the overload limit for
the time defined in parameter
Recovery - Fault
Overload condition triggers the overload recovery sequence.
In case recovery routine helps, motor speed returns to
production speed. If not, drive generates the event
fault which immediately trips the drive.
Defines overload curve point 1 load limit active at
corresponding speed set in parameter
.
0.00
-30000.00...
30000.0 0
Overload curve point 1.
10 = 1
Defines overload curve point 2 load limit active at
corresponding speed set in parameter
.
0.00
-30000.00...
30000.0 0
Overload curve point 2.
10 = 1
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...