Parameters 187
26.02
Const speed sel1
When bit 0 of parameter
is 0
(Separate), selects a source that activates constant speed 1.
When bit 0 of parameter
is 1
(Packed), this parameter and parameters
select three sources whose
states activate constant speeds as follows:
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
Const
Bit pointer setting (see
on page
).
-
Pointer
26.03
Const speed sel2
When bit 0 of parameter
is 0
(Separate), selects a source that activates constant speed 2.
When bit 0 of parameter
is 1
(Packed), this parameter and parameters
and
select three sources that
are used to activate constant speeds. See table at parameter
.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
Const
Bit pointer setting (see
on page
).
-
Pointer
26.04
Const speed sel3
When bit 0 of parameter
is 0
(Separate), selects a source that activates constant speed 3.
When bit 0 of parameter
is 1
(Packed), this parameter and parameters
and
select three sources that
are used to activate constant speeds. See table at parameter
.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
No.
Name/Value
Description
FbEq
Source defined
by par.
Constant speed active
0
0
0
None
1
0
0
Constant speed 1
0
1
0
Constant speed 2
1
1
0
Constant speed 3
0
0
1
Constant speed 4
1
0
1
Constant speed 5
0
1
1
Constant speed 6
1
1
1
Constant speed 7
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...