Parameters 117
06.02
Status word2
Status word 2 of the drive.
-
No.
Name/Value
Description
FbEq
Bit
Name
Information
0
Start act
1 = Drive start command is active.
0 = Drive start command is inactive.
1
Stop act
1 = Drive stop command is active.
0 = Drive stop command is inactive.
2
Ready relay 1 = Ready to function: run enable signal on, no fault, emergency stop signal
off, no ID run inhibition. Connected by default to DIO1 by par.
0 = Not ready to function.
3
Modulating 1 = Modulating: IGBTs are controlled, ie. the drive is RUNNING.
0 = No modulation: IGBTs are not controlled.
4
Ref running 1 = Normal operation is enabled. Running. Drive follows the given
reference.
0 = Normal operation is disabled. Drive is not following the given reference
(eg. in magnetization phase drive is modulating).
5
Jogging
1 = Jogging function 1 or 2 is active.
0 = Jogging function is inactive.
6
Off1
1 = Emergency stop OFF1 is active.
0 = Emergency stop OFF1 is inactive.
7
Start inh
mask
) start inhibit is active.
0 = No maskable start inhibit is active.
8
Start inh
nomask
1 = Non-maskable start inhibit is active.
0 = No non-maskable start inhibit is active.
9
Chrg rel
closed
1 = Charging relay is closed.
0 = Charging relay is open.
10
Sto act
1 = Safe torque off function is active. See parameter
.
0 = Safe torque off function is inactive.
11
Reserved
12
Ramp in 0
1 = Ramp Function Generator input is forced to zero.
0 = Normal operation.
13
Ramp hold 1 = Ramp Function Generator output is held.
0 = Normal operation.
14
Ramp out 0 1 = Ramp Function Generator output is forced to zero.
0 = Normal operation.
15…31 Reserved
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...