Parameters 189
64.02
PVL filt time
Peak value logger filtering time. See parameter
0.00 … 120.00 s
Peak value logger filtering time.
100 = 1 s
64.03
Reset loggers
Selects the signal to reset the peak value logger and
amplitude logger 2. (Amplitude logger 1 cannot be reset.)
Const
Bit pointer setting (see
on page
). -
Pointer
64.04
AL signal
Selects the signal to be monitored by amplitude logger 2. The
signal is sampled at 200 ms intervals when the drive is
running.
The results are displayed by parameters
. Each
parameter represents an amplitude range, and shows what
portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter
.
Parameter
resets both the peak value
logger and amplitude logger 2. The latest time the loggers
were reset is stored into parameter
.
Note:
Amplitude logger 1 is fixed to monitor motor current
(
). The results are displayed by
. 100% of the signal value
corresponds to the nominal output current of the drive (see
the appropriate
Hardware Manual)
.
Speed rpm
).
1073742081
Speed %
(see page
).
1073742082
Frequency
).
1073742083
Current
(see page
).
1073742084
Current %
(see page
).
1073742085
Torque
(see page
1073742086
Dc-voltage
(see page
1073742087
Power inu
).
1073742102
Power motor
(see page
).
1073742103
Process act
(see page
).
1073742851
Proc PID out
(see page
1073742853
Pointer
Value pointer setting (see
on page
).
-
64.05
AL signal base
Defines the signal value that corresponds to 100% amplitude.
0.00 … 32768.00
Signal value corresponding to 100%.
100 = 1
64.06
PVL peak value1
Peak value recorded by the peak value logger.
-32768.00 …
32768.00
Peak value.
100 = 1
64.07
Date of peak
The date on which the peak value was recorded.
01.01.80 …
Peak occurrence date (dd.mm.yy).
1 = 1 d
64.08
Time of peak
The time at which the peak value was recorded.
00:00:00 …
23:59:59
Peak occurrence time.
1 = 1 s
No.
Name/Value
Description
FbEq