32
32 Automatic reset
Defines conditions for automatic fault resets.
32.01
Autoreset sel
Selects faults that are automatically reset. The parameter is a
16-bit word with each bit corresponding to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
The bits of the binary number correspond to the following
faults:
32.02
Number of trials
Defines the number of automatic fault resets the drive
performs within the time defined by parameter
0 … 5
Number of automatic resets.
1 = 1
32.03
Trial time
Defines the time for the automatic fault reset function. See
parameter
.
1.0 … 600.0 s
Time for automatic resets.
10 = 1 s
32.04
Delay time
Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter
.
0.0 … 120.0 s
Resetting delay.
10 = 1 s
33
33 Supervision
Configuration of signal supervision.
33.01
Superv1 func
Selects the mode of supervision 1.
Disabled
Supervision 1 not in use.
0
Low
When the signal selected by parameter
falls below the value of parameter
, bit 0 of
is activated.
1
High
When the signal selected by parameter
exceeds the value of parameter
, bit 0 of
is activated.
2
Abs Low
When the absolute value of the signal selected by parameter
falls below the value of parameter
, bit 0 of
is activated.
3
Abs High
When the absolute value of the signal selected by parameter
exceeds the value of parameter
, bit 0 of
is activated.
4
33.02
Superv1 act
Selects the signal to be monitored by supervision 1. See
parameter
.
Speed rpm
).
1073742081
Speed %
(see page
).
1073742082
Frequency
).
1073742083
Current
(see page
).
1073742084
Current %
(see page
).
1073742085
No.
Name/Value
Description
FbEq
Bit
Fault
0
Overcurrent
1
Overvoltage
2
Undervoltage
3
AI min
4
Line converter
5
External fault