Technical data
17
Technical data
PPCS links, V1…V10
(V21…V36)*
Agilent Technologies Versatile Link series 10 MBd optical transmitters & receivers
Protocol: PPCS, 8 Mbit/s
Transmitter current: 30 mA
*with APBU-44CE only
Max. optical cable (POF) length: 15 m
DDCS link, V11 & V12
Agilent Technologies Versatile Link series 10 MBd optical transmitter & receiver
Protocol: DDCS, 1/2/4/8 Mbit/s
Transmitter current: 30/50 mA (“Short”/”Long”, switch-selectable)
Max. optical cable (POF) length: 20/30 m (depending on transmitter current setting)
Max. optical cable (HCS) length: 50/200 m (depending on transmitter current setting)
In redundant control, this channel is used as a secondary PPCS link (CNTL 2)
Trigger port, V13 & V14
Agilent Technologies Versatile Link series 10 MBd optical transmitter & receiver
Transmitter current: 30 mA
Max. optical cable (POF) length: 20 m
Max. optical cable (HCS) length: 50 m
Power supply input, X1
Two redundant diode-separated inputs
Internal protection: Microfuse, 1 A, slow
Operating voltage: 24 VDC ±10%
Current consumption:
200 mA typical, 250 mA max. (APBU-44C)
350 mA typical, 400 mA max. (APBU-44CE)
4-pin detachable screw terminal block. Maximum wire size: 2.5 mm
2
.
DDCS address switches,
S1 & S2
Two 16-position rotary switches representing the numbers 0…F (hex)
S1: 4 most significant bits of the address; S2: 4 least significant bits of the address
Mode switch, S3
Piano-type 6-way DIP switch
Applicable standards
Safety requirements: EN 50178 Electronic equipment for use in power installations
IEC 61800-5-1 Semiconductor power converters for adjustable frequency drive
systems
UL 508 A Industrial Control Panels
EMC emission: EN 61000-6-4 (IEC 61000-6-4) Emission for industrial environment
EMC immunity: EN 61000-6-2 (IEC 61000-6-2) Immunity for industrial environment
Memory backup battery
CR 2032 (3 V, 220 mAh); on-off switch
Data retention time: More than 6 months with new battery
Operating temperature
+0...+50 °C (free air circulation)
Dimensions (L × W × D)
275 × 102 × 68 mm
Mounting
On 7.5 × 35 mm mounting rail (EN50022), vertical or horizontal
Other features
Conformal coating as standard
Summary of Contents for ACS800 Multidrive
Page 1: ...ACS800 Multidrive Hardware Manual APBU 44C E PPCS Branching and Datalogger Unit ...
Page 2: ......
Page 4: ......
Page 6: ...Table of contents 6 ...
Page 16: ...Installation 16 ...
Page 18: ...Technical data 18 ...
Page 20: ...Dimensions 20 ...
Page 21: ......