The internal cooling circuit 115
Additional US and Canada requirements
To comply with the requirements of UL508C, install a pressure relief valve in the liquid
cooling unit. The recommended discharge rate of the valve is 8…10 bar (800…1000 kPa).
Coolant temperature control
The temperature of the coolant in the internal cooling circuit must be kept within the limits
specified in
on page
. Note that the minimum temperature is dependent
on ambient temperature and relative humidity.
The following diagram shows an example of coolant temperature control using the three-
way valve in the external cooling circuit. Part of the infeed coolant flow is directed into the
return pipe through a three-way valve without letting it circulate in heat exchanger if the
coolant in the internal circuit is too cold.
Mechanical installation
Coupling the internal cooling circuit to a customer cooling unit
Connect the external cooling circuit directly to the coupling pipes on the side of the
converter. Lay liquid piping with extreme care. Secure the pipes properly mechanically and
check for leaks.
Infeed
Bypass valve
TC
Return
External circuit
Internal circuit
Heat
exchanger
Summary of Contents for ACS800-67LC
Page 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 52: ...52 Mechanical installation ...
Page 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Page 92: ...92 Maintenance 4 6 5 5 ...
Page 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Page 109: ...Maintenance 109 5 6 7 ...
Page 131: ...Technical data 131 Declaration of incorporation ...
Page 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Page 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Page 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Page 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Page 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Page 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Page 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Page 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Page 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Page 147: ...Dimension drawings 147 Option 2H372 ...
Page 148: ...148 Dimension drawings Option 3H372 ...
Page 149: ...Dimension drawings 149 Option 1H373 ...
Page 150: ...150 Dimension drawings Option 2H373 ...
Page 151: ...Dimension drawings 151 Option 3H373 ...