The internal cooling circuit 117
15. Repeat steps 13 to 15 a few times until all air is let out of the cooling circuit. Listen for
a humming sound and/or feel the piping for vibration to find out if there is still air left in
the circuit.
16. Open the bleed valve in the cabinet. Check that coolant comes out, not air. Lead the
bleed hose into a bucket or other suitable container.
Draining the internal cooling circuit
The internal cooling circuit can be drained through the drain valves in auxiliary control
cubicle.
WARNING!
High-pressure warm coolant may be present in the internal cooling
circuit. No work on the cooling circuit is allowed until the pressure is lowered down
by stopping the pumps and draining coolant.
1. Lead the bleed and drain hoses to buckets or other suitable containers. Extend the
standard hoses if necessary.
Note:
Draining liquid that contains eg, propylene glycol into the sewer system is not
allowed.
2. Open the bleed valves to let air displace the liquid.
3. If required, dry the piping with compressed oil-free air of less than 600 kPa (6 bar).
4. If the converter is to be stored in temperatures below 0 °C (32 °F),
•
dry the cooling circuit with air
•
fill the cooling circuit with a mixture of water, corrosion inhibitor and antifreeze
according to
Freeze protection and corrosion inhibition
below
•
drain the cooling circuit again.
Adding inhibitor
Add inhibitor in the internal circuit every second year. The amount to be added is 0.5% of
the total coolant quantity in the circuit. Use eg, Cortec VpCI-649 (by Cortec Corporation,
www.cortecvci.com).
Specifications
Temperature limits
Ambient temperature:
See chapter
.
Minimum coolant inlet temperature for the converter:
Condensation is not allowed.
The minimum coolant temperature to avoid condensation (at an atmospheric pressure of
100 kPa (1 bar)) is shown below as a function of the relative humidity (
φ
) and the ambient
temperature (
T
air
).
Summary of Contents for ACS800-67LC
Page 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 52: ...52 Mechanical installation ...
Page 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Page 92: ...92 Maintenance 4 6 5 5 ...
Page 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Page 109: ...Maintenance 109 5 6 7 ...
Page 131: ...Technical data 131 Declaration of incorporation ...
Page 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Page 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Page 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Page 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Page 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Page 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Page 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Page 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Page 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Page 147: ...Dimension drawings 147 Option 2H372 ...
Page 148: ...148 Dimension drawings Option 3H372 ...
Page 149: ...Dimension drawings 149 Option 1H373 ...
Page 150: ...150 Dimension drawings Option 2H373 ...
Page 151: ...Dimension drawings 151 Option 3H373 ...