108 Practical examples
Setting the parameters according to grid code
Parameter setting examples in cases of Spanish, Italian and United Kingdom grid codes
are given below.
Spanish grid code
Parameter
Setting
Control program AJXC2330 (or newer) parameters:
30.05 AC OVERVOLT TRIP
793.5 V
30.06 AC UNDERVOLT TRIP
68.9999 V
30.07 AC OVERFREQ TRIP
53 Hz
30.08 AC UNDERFREQ TRIP
47 Hz
31.01 CROWBAR HW TYPE
ACTIVE CB
32.01 GRID SUPPORT MODE
MAX. Up-p
32.02 RT MONITOR SIGNAL
MIN. Up-p
32.03 RT U/Un LEVEL1
80%
32.04 RT U/Un LEVEL2
9.99999%
32.05 RT U/Un LEVEL 3
70%
32.06 RT U/Un DELTA t1
3000 ms
32.07 RT U/Un DELTA t2
600 ms
32.08 RT U/Un DELTA t3
12000 ms
32.09 RT U/Un DELTA t4
3000 ms
32.10 RT U/Un LEVELHYST
5%
32.11 GS U/Un LEVEL 1
85%
32.12 GS U/Un LEVEL 2
50%
32.13 GS U/Un LEVEL 3
25%
32.14 GS U/Un LEVEL 4
15%
32.15 GS U/Un LEVEL 5
110%
32.16 GS U/Un LEVEL 6
120%
32.17 GS IQREF LEVEL 1
9.99999%
32.18 GS IQREF LEVEL 2
100%
32.19 GS IQREF LEVEL 3
100%
32.20 GS IQREF LEVEL 4
100%
32.21 GS IQREF LEVEL 5
-20%
32.24 GS TIME AFTER DIP
500 ms
32.25 KVAR RISE TIME
120 ms
32.26 TORQUE RISE TIME
99.9999 ms
32.27 TMAX/TN (LVRT)
4.99997%
32.28 TMIN/TN (LVRT)
3.00002%
32.29 RT MAX POWER
100%
32.30 IR MAX PEAK LEVEL
2285.57 A
32.31 IR MAXSLOPE SCALE
507.903 A
32.32 U- / U+ START DIS
45%
32.33 U(RMS) START DIS
9.99999%
32.41 ENVELOPE PAR SEL
PAR 1
Summary of Contents for ACS800-67
Page 4: ......
Page 76: ...76 Start up with medium voltage stator ...
Page 99: ...Practical examples 99 1 4 4 3 2 5 6 7 ...
Page 106: ...106 Practical examples Counterclockwise rotation at drive end D end Power cabinet Encoder ...
Page 118: ...118 Tracing the source of warnings limits and faults ...
Page 120: ...Contact us www abb com windconverters 3AUA0000095094 Rev B EN 2017 12 31 ...