Practical examples 103
If parameter download fails, an error note appears:
1. Compare the parameters to the parameter settings given in section
2. Do the start-up checks and settings as instructed in chapters
and
Start-up with medium voltage stator
.
Communication parameter settings
Rotor-side converter
In addition, the fieldbus module settings must be made. See the
ACS800-67(LC) doubly-
fed induction generator control program firmware manual
[3AUA0000071689 (English)].
Parameter
Setting
Note
16.20 GRID CONNECT MODE
MCB1+MCB3/B
31.01 CROWBAR HW TYPE
ACTIVE CB
2 ACTIVE CBs
In case of one crowbar
In case of two crowbars
70.15 CH3 NODE ADDR
11
70.21 CH4 NODE ADDR
11
97.01 DEVICE NAME
INU 800 xxxx_7LC
Use the correct converter type
99.27 MAX MEAS FLUX
2.43936
2.805279
Default value when using
NUIM-62C board
To be set manually when using
NUIM-10C board
99.28 MAX MEAS IS
3293
4116
4939
6585
6585
Set according to power type.
See also section
.