46 Start-up with low voltage stator
NUIM board in use (grid-side converter control program
IXXR72xx):
• Enable the grid-side converter parameter lock by setting parameter
16.03 PASS CODE to 2303. Parameter groups 100…202 become
visible when the parameter lock is enabled.
16.03
PASS CODE
NAMU / BAMU board in use (grid-side converter control program
IWXR74xx):
• Parameter groups needed are visible automatically.
Check grid-side converter supply voltage measurement:
NUIM board in use (grid-side converter control program
IXXR72xx):
• Set grid-side converter parameter 138.04 CASCADE MEAS ENA
to ON and
• Set grid-side converter parameter 138.01 NAMU BOARD ENABLE
to OFF.
See grid-side converter
parameter list:
138.04 CASCADE MEAS
ENA
138.01 NAMU BOARD
ENABLE
NAMU / BAMU board in use (grid-side converter control program
IWXR74xx):
• Set grid-side converter parameter 40.04 PHASE MEAS ENA to
OFF and
• Set grid-side converter parameter 40.02 NAMU BOARD ENABLE
to ON if NAMU board is in use.
• Set grid-side converter parameter 40.03 BAMU BOARD ENABLE
to ON if BAMU board is in use.
40.04 PHASE MEAS ENA
40.02 NAMU BOARD
ENABLE
NUIM board in use (grid-side converter control program
IXXR72xx):
Check grid-side converter parameter 01.11 MAINS VOLTAGE value
(= mains voltage received from the rotor-side converter). If the
voltage level is correct, communication between rotor-side and grid-
side converters is OK.
01.11 MAINS VOLTAGE
NAMU / BAMU board in use (grid-side converter control program
IWXR74xx):
Check grid-side converter parameter 01.11 MAINS VOLTAGE value
(= mains voltage received from the rotor-side converter). If the
voltage level is correct, measurement is OK.
Summary of Contents for ACS800-67
Page 4: ......
Page 76: ...76 Start up with medium voltage stator ...
Page 99: ...Practical examples 99 1 4 4 3 2 5 6 7 ...
Page 106: ...106 Practical examples Counterclockwise rotation at drive end D end Power cabinet Encoder ...
Page 118: ...118 Tracing the source of warnings limits and faults ...
Page 120: ...Contact us www abb com windconverters 3AUA0000095094 Rev B EN 2017 12 31 ...