Operation
79
Actual signals and parameters of the line converter in the motor-side converter
control program
No.
Name/Value
Description
FbEq
Def.
09 ACTUAL SIGNALS
Signals from the line converter.
09.12
LCU ACT SIGNAL 1
Line converter signal selected by par. 95.08 LCU PAR1 SEL.
1 = 1
106
09.13
LCU ACT SIGNAL 2
Line converter signal selected by par. 95.09 LCU PAR2 SEL.
1 = 1
110
95 HARDWARE SPECIF
Line converter references and actual signal selections.
95.06
LCU Q POW REF
Reactive power reference for the line converter i.e. the value for
par. 24.02 Q POWER REF2 in the IGBT Supply Control Program.
Scaling example 1: 10000 equals to a value of 10000 of parameter
24.02 Q POWER REF2 and 100% of par. 24.01 Q POWER REF
(i.e. 100% of the converter nominal power given in par. 04.06
CONV NOM POWER) when par. 24.03 Q POWER REF2 SEL is
set to PERCENT.
Scaling example 2: Par. 24.03 Q POWER REF2 SEL is set to kVAr.
A value of 1000 of par. 95.06 equals to 1000 kVAr of par. 24.02 Q
POWER REF2. Value of par. 24.01 Q POWER REF is then 100 ·
(1000 kVAr divided by converter nominal power in kVAr)%.
Scaling example 3: Par. 24.03 Q POWER REF2 SEL is set to PHI.
A value of 10000 of par. 95.06 equals to a value of 100 deg of
parameter 24.02 Q POWER REF2 which is limited to 30 deg. The
value of par. 24.01 Q POWER REF will be determined
approximately according to the following equation where
P
is read
from actual signal 1.09 POWER:
0
-10000 ... +10000
Setting range.
1 = 1
95.07
LCU DC REF (V)
DC voltage reference for line converter i.e. the value for par. 23.01
DC VOLT REF.
0
0 … 1100
Setting range in volts.
1 = 1 V
95.08
LCU PAR1 SEL
Selects the line-side converter address from which actual signal
09.12 LCU ACT SIGNAL 1 is read.
106
0 … 10000
Parameter index.
1 = 1
95.09
LCU PAR2 SEL
Selects the line-side converter address from which actual signal
09.13 LCU ACT SIGNAL 2 is read.
110
0 … 10000
Parameter index.
1 = 1
30
cos
P
S
---
P
P
2
Q
2
+
------------------------
=
=
30 deg
S
Q
P
Positive reference 30 deg denotes capacitive load.
Negative reference 30 deg denotes inductive load.
-10000
+10000
0
30 (deg)
3000
-3000
10
1000
-1000
-10
-30
0
Par. 95.06
Par. 24.02
Summary of Contents for ACS800-11
Page 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 30: ...The ACS800 11 U11 30 ...
Page 36: ...Mechanical installation 36 ...
Page 54: ...Planning the electrical installation 54 ...
Page 74: ...Installation checklist 74 ...
Page 84: ...Operation 84 ...
Page 104: ...Technical data 102 ...
Page 108: ...Dimensional drawings 106 ...
Page 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Page 112: ...External 24 V power supply for the RMIO board 110 ...
Page 113: ......