Planning the electrical installation
31
EU
To meet the European Union Directives, according to standard EN 60204-1, Safety
of Machinery, the disconnecting device must be one of the following types:
• a switch-disconnector of utilization category AC-23B (EN 60947-3)
• a disconnector that has an auxiliary contact that in all cases causes switching
devices to break the load circuit before the opening of the main contacts of the
disconnector (EN 60947-3)
• a circuit breaker suitable for isolation in accordance with EN 60947-2.
US
The disconnecting means must conform to the applicable safety regulations.
Fuses
See section
Thermal overload and short-circuit protection
Thermal overload and short-circuit protection
The drive protects itself and the input and motor cables against thermal overload
when the cables are dimensioned according to the nominal current of the drive. No
additional thermal protection devices are needed.
WARNING!
If the drive is connected to multiple motors, a separate thermal overload
switch or a circuit breaker must be used for protecting each cable and motor. These
devices may require a separate fuse to cut off the short-circuit current.
The drive protects the motor cable and the motor in a short-circuit situation when the
motor cable is dimensioned according to the nominal current of the drive.
Mains cable (AC line cable) short-circuit protection
Always protect the input cable with fuses. Size the fuses according to local safety
regulations, appropriate input voltage and the rated current of the drive (see
Technical Data)
.
ACS800-01/U1, ACS800-02/U2 without enclosure extension and ACS800-04/U4
When placed at the distribution board, standard gG (US: CC or T for the ACS800-
U1; T or L for the ACS800-U2 and the ACS800-U4) fuses will protect the input cable
in short-circuit situations, restrict drive damage and prevent damage to adjoining
equipment in case of a short-circuit inside the drive.
Summary of Contents for ACS800-02
Page 1: ...ACS800 Hardware Manual ACS800 02 Drives 45 to 500 kW ACS800 U2 Drives 60 to 600 HP ...
Page 4: ......
Page 10: ...Safety instructions 10 ...
Page 20: ...About this manual 20 ...
Page 26: ...The ACS800 02 U2 26 ...
Page 42: ...Planning the electrical installation 42 ...
Page 76: ...Installation checklist 76 ...
Page 106: ...Technical data 106 ...
Page 108: ...Dimensional drawings 108 Frame size R7 US gland conduit plate 64579746 H ...
Page 109: ...Dimensional drawings 109 Frame size R8 3AFE 64564161 D US gland conduit plate ...
Page 110: ...Dimensional drawings 110 Frame size R7 with enclosure extension bottom entry 64625942 1 2 B ...
Page 111: ...Dimensional drawings 111 64625942 2 2 C ...
Page 112: ...Dimensional drawings 112 Frame size R7 with enclosure extension top entry 64626264 1 2 C ...
Page 113: ...Dimensional drawings 113 64626264 2 2 C ...
Page 115: ...Dimensional drawings 115 3AFE 64626388 2 2 B ...
Page 116: ...Dimensional drawings 116 Frame size R8 with enclosure extension top entry 3AFE 64626370 1 2 C ...
Page 117: ...Dimensional drawings 117 3AFE 64626370 2 2 C ...
Page 118: ...Dimensional drawings 118 ...
Page 127: ......