ACS580-0P 3R Irrigation Packaged Drive
21
Application Guides
Application Guides - Hand - Auto Macro
1...10 kohm
2)
3)
3)
3)
4)
max.
500 ohm
X1
Reference voltage and analog inputs and outputs
1
SCR
Signal cable shield (screen)
2
AI1
Ext. speed/freq, reference (Hand):
0...10 V
5)
3
AGND
Analog input circuit common
4
+10V
Reference voltage 10 V DC
5
AI2
Ext. speed/freq, ref. (Auto):
4...20 mA
1, 5)
6
AGND
Analog input circuit common
7
AO1
Output frequency:
0...20 mA
5)
8
AO2
Motor current:
0...20 mA
9
AGND
Analog output circuit common
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
Auxiliary voltage 24 V DC, max. 250 mA
11
DGND
Auxiliary voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1) (Hand)
14
DI2
Forward (0) / Reverse (1) (Hand)
15
DI3
Hand control (0) / Auto control (1)
16
DI4
Run enable
; if 0, drive stops
17
DI5
Forward (0) / Reverse (1) (Auto)
18
DI6
Stop (0) / Start (1) (Auto)
X6, X7, X8
Relay outputs
19
RO1C
Ready run
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Running
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Fault (-1)
250 V AC / 30 V DC
2 A
26
RO3A
27
RO3B
X5
Embedded fieldbus
29
B+
Embedded Modbus RTU (EIA-485).
30
A-
31
DGND
S4
TERM
Serial data link termination switch
S5
BIAS
Serial data link bias resistors switch
X4
Safe torque off
34
OUT1
Safe torque off. Factory connection. Both circuits must
be cloased for the drive to start.
35
OUT2
36
SGND
37
IN1
38
IN2
X10
24 V AC/DC
40
24 V AC/DC+ in
R6...R11 only: Ext. 24V AC/DC input to power up the
control unit when the main supply is disconnected.
41
24 V ac/dc* in
Notes:
1.
The signal source is powered externally.
See the manufacturer’s instructions. To use
sensors supplied by the drive aux. voltage
output, see chapter Electrical installation,
section Connection examples of two-wire
and three-wire sensors in the Hardware
manual of the drive.
2.
Ground the outer shield of the cable 360
degrees under the grounding clamp on the
grounding shelf for the control cables.
3.
Connected with jumpers at the factory.
4.
Only frames R6…R11 have terminals 40
and 41 for external 24 V AC/DC input.
5.
Select voltage or current for inputs AI1 and
AI2 and output AO1 with parameters 12.15,
12.25 and 13.15, respectively.