Parameters 301
DI6
Digital input DI6 (
, bit 5).
7
Timed function 1
Bit 0 of
18
Timed function 2
Bit 1 of
19
Timed function 3
Bit 2 of
20
Supervision 1
Bit 0 of
(see page
21
Supervision 2
Bit 1 of
(see page
22
Supervision 3
Bit 2 of
(see page
23
). -
Inverts the input of the process PID controller.
0 = Deviation not inverted (Deviation = Setpoint - Feedback)
1 = Deviation inverted (Deviation = Feedback - Setpoint)
See also section
Sleep and boost functions for process PID
Not inverted
(Ref - Fbk)
0.
0
Inverted (Fbk - Ref) 1.
1
). -
Defines the gain for the process PID controller. See
parameter
.
1.00
0.01…100.00
Gain for PID controller.
100 = 1
Defines the integration time for the process PID controller.
This time needs to be set to the same order of magnitude as
the reaction time of the process being controlled, otherwise
instability will result.
Note:
Setting this value to 0 disables the “I” part, turning the
PID controller into a PD controller.
60.0 s
0.0…9999.0 s
Integration time.
1 = 1 s
No.
Name/Value
Description
Def/FbEq16
Ti
O
I
G × I
G × I
I = controller input (error)
O = controller output
G = gain
Ti = integration time
Time
Error/Controller output
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...