248 Parameters
Selects a source that switches between the two sets of
acceleration/deceleration times defined by parameters
.
0 = Acceleration time 1 and deceleration time 1 are in force
1 = Acceleration time 2 and deceleration time 2 are in force
Acc/Dec time 1
0
0
Acc/Dec time 2
1
1
DI1
Digital input DI1 (
, bit 0)
2
DI2
Digital input DI2 (
, bit 1)
3
DI3
Digital input DI3 (
, bit 2)
4
DI4
Digital input DI4 (
, bit 3)
5
DI5
Digital input DI5 (
, bit 4)
6
DI6
Digital input DI6 (
, bit 5)
7
FBA A
Only for the Transparent16 or Transparent32 profile.
Transparent16 or Transparent32 control word bit received
through the fieldbus A interface.
18
EFB DCU CW bit
10
Only for the DCU profile. DCU control word bit 10 received
through the embedded fieldbus interface.
20
Source selection (see
). -
Defines acceleration time 1 as the time required for the
frequency to change from zero to the frequency defined by
parameter
. After this frequency has
been reached, the acceleration continues with the same rate
to the value defined by parameter
.
If the reference increases faster than the set acceleration
rate, the motor will follow the acceleration rate.
If the reference increases slower than the set acceleration
rate, the motor frequency will follow the reference.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to exceed
the drive torque limits.
20.000 s
0.000…1800.000 s
Acceleration time 1.
10 = 1 s
Defines deceleration time 1 as the time required for the
frequency to change from the frequency defined by
parameter
(
not
from parameter
) to zero.
If there is any doubt about the deceleration time being too
short, ensure that DC overvoltage control (
) is on.
Note:
If a short deceleration time is needed for a high inertia
application, the drive should be equipped with braking
equipment such as a brake chopper and brake resistor.
20.000 s
0.000…1800.000 s
Deceleration time 1.
10 = 1 s
Defines acceleration time 2. See parameter
.
60.000 s
0.000…1800.000 s
Acceleration time 2.
10 = 1 s
Defines deceleration time 2. See parameter
60.000 s
0.000…1800.000 s
Deceleration time 2.
10 = 1 s
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...