Parameters 227
Defines acceleration time 1 as the time required for the speed
to change from zero to the speed defined by parameter
(
not
).
If the speed reference increases faster than the set
acceleration rate, the motor speed will follow the acceleration
rate.
If the speed reference increases slower than the set
acceleration rate, the motor speed will follow the reference.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to exceed
the drive torque limits.
20.000
0.000…1800.000 s
Acceleration time 1.
10 = 1
Defines deceleration time 1 as the time required for the speed
to change from the speed defined by parameter
not
from parameter
) to zero.
If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the reference.
If the reference changes faster than the set deceleration rate,
the motor speed will follow the deceleration rate.
If the deceleration rate is set too short, the drive will
automatically prolong the deceleration in order not to exceed
drive torque limits (or not to exceed a safe DC link voltage). If
there is any doubt about the deceleration time being too
short, ensure that DC overvoltage control is on (parameter
).
Note:
If a short deceleration time is needed for a high inertia
application, the drive should be equipped with braking
equipment such as a brake chopper and brake resistor.
20.000
0.000…1800.000 s
Deceleration time 1.
10 = 1
Defines acceleration time 2. See parameter
.
60.000
0.000…1800.000 s
Acceleration time 2.
10 = 1
Defines deceleration time 2. See parameter
60.000
0.000…1800.000 s
Deceleration time 2.
10 = 1
Defines the acceleration time for the jogging function ie. the
time required for the speed to change from zero to the speed
value defined by parameter
.
See section
60.000
0.000…1800.000 s
Acceleration time for jogging.
10 = 1
Defines the deceleration time for the jogging function ie. the
time required for the speed to change from the speed value
defined by parameter
to zero.
See section
60.000
0.000…1800.000 s
Deceleration time for jogging.
10 = 1
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...