210 Parameters
Const time
The drive pre-magnetizes the motor before start. The pre-
magnetizing time is defined by parameter
. This mode should be selected if constant
pre-magnetizing time is required (e.g. if the motor start must
be synchronized with the release of a mechanical brake).
This setting also guarantees the highest possible break-away
torque when the pre-magnetizing time is set long enough.
WARNING!
The drive will start after the set
magnetizing time has passed even if motor
magnetization is not completed. In applications where
a full break-away torque is essential, ensure that the constant
magnetizing time is long enough to allow generation of full
magnetization and torque.
1
Automatic
Automatic start guarantees optimal motor start in most cases.
It includes the flying start function (starting into a rotating
motor) and the automatic restart function. The drive motor
control program identifies the flux as well as the mechanical
state of the motor and starts the motor instantly under all
conditions.
Note:
is set to
,
no flying start or automatic restart is possible unless
parameter
is set to
2
Defines the pre-magnetization time when
• parameter
is set to
(in vector
motor control mode), or
• parameter
(in
scalar motor control mode).
After the start command, the drive automatically
premagnetizes the motor for the set time. To ensure full
magnetizing, set this parameter to the same value as, or
higher than, the rotor time constant. If not known, use the
rule-of-thumb value given in the table below:
Note:
This parameter cannot be changed while the drive is
running.
500
0…10000 ms
Constant DC magnetizing time.
1 = 1
Selects the way the motor is stopped when a stop command
is received.
Additional braking is possible by selecting flux braking (see
parameter
).
Coast
Stops by switching off the output semiconductors of the drive.
The motor coasts to a stop.
WARNING!
If a mechanical brake is used, ensure it is
safe to stop the drive by coasting.
0
Ramp
Stops along the active deceleration ramp. See parameter
group
on page
on page
.
1
No.
Name/Value
Description
Def/FbEq16
Motor rated power
Constant magnetizing time
< 1 kW
> 50 to 100 ms
1 to 10 kW
> 100 to 200 ms
10 to 200 kW
> 200 to 1000 ms
200 to 1000 kW
> 1000 to 2000 ms
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...