Control panels
Copy mode
The Basic Control Panel can store a full set of drive parameters and up to two user
sets of drive parameters to the control panel. The control panel memory is non-
volatile.
In the Copy mode, you can:
• copy all parameters from the drive to the control panel (uL – Upload). This
includes all defined user sets of parameters and internal (not adjustable by the
user) parameters such as those created by the ID Run.
• restore the full parameter set from the control panel to the drive (dL A – Download
All). This writes all parameters, including the internal non-user-adjustable motor
parameters, to the drive. It does not include the user sets of parameters.
Note:
Only use this function to restore a drive, or to transfer parameters to
systems that are identical to the original system.
• copy a partial parameter set from the control panel to a drive (dL P – Download
Partial). The partial set does not include user sets, internal motor parameters,
parameters
, nor any
and
parameters.
The source and target drives and their motor sizes do not need to be the same.
• copy USER S1 parameters from the control panel to the drive (dL u1 – Download
User Set 1). A user set includes
parameters and the
internal motor parameters.
The function is only shown on the menu when User Set 1 has been first saved
using parameter
APPLIC
MACRO
(see section
on page
) and then uploaded to panel.
• copy USER S2 parameters from the control panel to the drive (dL u2 – Download
User Set 2). As dL u1 – Download User Set 1 above.
• start, stop, change the direction and switch between local and remote control.
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...