ACS550 User’s Manual
273
Technical data
Motor cable length for 600 V drives
The table below shows the maximum motor cable lengths for 600 V drives with
different switching frequencies. As the 600 V drives are not CE approved, cable
lengths for EMC limits are not given.
WARNING!
Using a motor cable longer than specified in the table above may cause
permanent damage to the drive.
Motor thermal protection
According to regulations, the motor must be protected against thermal overload and
the current must be switched off when overload is detected. The drive includes a
motor thermal protection function that protects the motor and switches off the current
when necessary. Depending on a drive parameter value (see
), the function either monitors a calculated temperature value (based
on a motor thermal model) or an actual temperature indication given by motor
temperature sensors. The user can tune the thermal model further by feeding in
additional motor and load data.
The most common temperature sensors are:
• motor sizes IEC180…225: thermal switch (e.g. Klixon)
• motor sizes IEC200…250 and larger: PTC or PT100.
Ground fault protection
ACS550 internal fault logic detects ground faults in the drive, motor, or motor cable.
This fault logic:
• is NOT a personal safety or fire protection feature
• can be disabled using parameter 3017
EARTH
FAULT
• could be tripped by leakage currents (input power to ground) associated with long
high capacitance motor cables.
Maximum cable length for 600 V drives
Frame
size
Operational limits
1/4 kHz
8/12 kHz
m
ft
m
ft
R2
100
330
100
330
R3…R4
200
660
100
330
R6
300
980
150
2
490
2
2
12 kHz switching frequency is not available.
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...