ACS550 User’s Manual
245
Diagnostics
2
DC
OVERVOLT
Intermediate circuit DC voltage is excessive. Check for and correct:
• Static or transient overvoltages in the input power supply.
• Insufficient deceleration time (parameters 2203
DECELER
TIME
1 and
2206
DECELER
TIME
2).
• Undersized brake chopper (if present).
• Verify that overvoltage controller is ON (using parameter 2005).
3
DEV
OVERTEMP
Drive heatsink is overheated. Temperature is at or above limit.
R1…R4 & R7/R8: 115 °C (239 °F)
R5/R6: 125 °C (257 °F)
Check for and correct:
• Fan failure.
• Obstructions in the air flow.
• Dirt or dust coating on the heat sink.
• Excessive ambient temperature.
• Excessive motor load.
4
SHORT
CIRC
Fault current. Check for and correct:
• A short-circuit in the motor cable(s) or motor.
• Supply disturbances.
5
RESERVED
Not used.
6
DC
UNDERVOLT
Intermediate circuit DC voltage is not sufficient. Check for and correct:
• Missing phase in the input power supply.
• Blown fuse.
• Undervoltage on mains.
7
AI
1
LOSS
Analog input 1 loss. Analog input value is less than
AI
1
FAULT
LIMIT
(3021).
Check for and correct:
• Source and connection for analog input.
• Parameter settings for
AI
1
FAULT
LIMIT
(3021) and 3001
AI
<
MIN FUNCTION
.
8
AI
2
LOSS
Analog input 2 loss. Analog input value is less than
AI
2
FAULT
LIMIT
(3022).
Check for and correct:
• Source and connection for analog input.
• Parameter settings for
AI
2
FAULT
LIMIT
(3022) and 3001
AI
<
MIN FUNCTION
.
9
MOT
OVERTEMP
Motor is too hot, based on either the drive’s estimate or on temperature
feedback.
• Check for overloaded motor.
• Adjust the parameters used for the estimate (3005…3009).
• Check the temperature sensors and
parameters.
10
PANEL
LOSS
Panel communication is lost and either:
• Drive is in local control mode (the control panel displays LOC), or
• Drive is in remote control mode (REM) and is parameterized to accept
start/stop, direction or reference from the control panel.
To correct check:
• Communication lines and connections.
• Parameter 3002
PANEL
COMM
ERR
.
• Parameters in
(if drive operation is REM).
Fault
code
Fault name in
panel
Description and recommended corrective action
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...