ACS550 User’s Manual
139
Group 29: MAINTENANCE TRIG
This group contains usage levels and trigger points. When usage reaches the set
trigger point, a notice displayed on the control panel signals that maintenance is due.
Code Description
2901
COOLING FAN TRIG
Sets the trigger point for the drive’s cooling fan counter.
• Value is compared to parameter 2902 value.
0.0 – Disables the trigger.
2902
COOLING FAN ACT
Defines the actual value of the drive’s cooling fan counter.
• When parameter 2901 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2901, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
2903
REVOLUTION TRIG
Sets the trigger point for the motor’s accumulated revolutions counter.
• Value is compared to parameter 2904 value.
0 – Disables the trigger.
2904
REVOLUTION ACT
Defines the actual value of the motor’s accumulated revolutions counter.
• When parameter 2903 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2903, a maintenance notice is
displayed on the panel.
0 – Resets the parameter.
2905
RUN TIME TRIG
Sets the trigger point for the drive’s run time counter.
• Value is compared to parameter 2906 value.
0.0 – Disables the trigger.
2906
RUN TIME ACT
Defines the actual value of the drive’s run time counter.
• When parameter 2905 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2905, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
2907
USER MWh TRIG
Sets the trigger point for the drive’s accumulated power consumption (in megawatt hours) counter.
• Value is compared to parameter 2908 value.
0.0 – Disables the trigger.
2908
USER MWh ACT
Defines the actual value of the drive’s accumulated power consumption (in megawatt hours) counter.
• When parameter 2907
has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2907, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...