102
ACS550 User’s Manual
0136
COMM VALUE 2
Free data location that can be written from serial link.
0137
PROCESS VAR 1
Process variable 1
• Defined by parameters in
0138
PROCESS VAR 2
Process variable 2
• Defined by parameters in
0139
PROCESS VAR 3
Process variable 3
• Defined by parameters in
0140
RUN TIME
The drive’s accumulated running time in thousands of hours (kh).
• Cannot be reset.
0141
MWH COUNTER
The drive’s accumulated power consumption in megawatt hours.
• Cannot be reset.
0142
REVOLUTION CNTR
The motor’s accumulated revolutions in millions of revolutions.
• Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0143
DRIVE ON TIME HI
The drive’s accumulated power-on time in days.
• Cannot be reset.
0144
DRIVE ON TIME LO
The drive’s accumulated power-on time in 2 second ticks (30 ticks = 60 seconds).
• Shown in format hh.mm.ss.
• Cannot be reset.
0145
MOTOR TEMP
Motor temperature in degrees Celsius / PTC resistance in ohms.
• Applies only if motor temperature sensor is set up.
• See parameter 3501.
0146
MECH ANGLE
Defines the motor shaft’s angular position to about 0.01° (32,768 divisions for 360°). The position is defined as 0 at
power up.
During operation the zero position can be set by:
• a Z-pulse input, if parameter 5010
Z
PLS
ENABLE
= 1 (
ENABLE
)
• parameter 5011
POSITION
RESET
, if parameter 5010
Z
PLS
ENABLE
= 2 (
DISABLE
)
• any status change of parameter 5002
ENCODER
ENABLE
.
0147
MECH REVS
A signed integer that counts full revolutions of the motor shaft. The value:
• increments when parameter 0146
MECH
ANGLE
changes from 32767 to 0
• decrements when parameter 0146
MECH
ANGLE
changes from 0 to 32767.
0148
Z PLS DETECTED
Encoder zero pulse detector. When a Z-pulse defines the zero position, the shaft must pass through the zero position
to trigger a Z-pulse. Until then, the shaft position is unknown (the drive uses the shaft position at power up as zero).
This parameter signals when parameter 0146
MECH
ANGLE
is valid. The parameter starts at 0 =
NOT
DETECTED
on
power-up and changes to 1 =
DETECTED
only if:
• parameter 5010
Z
PLS
ENABLE
= 1 (
ENABLE
) and
• an encoder Z-pulse has been detected.
0150
CB TEMP
Temperature of the drive control board in degrees Celsius.
Note:
Some drives have a control board (OMIO) that does not support this feature. These drives always show the
constant value of 25.0 °C.
Code Description
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...