ACS510 User’s Manual
195
Fieldbus Adapter
Actual Value Scaling
For Actual Values, scale the feedback integer using the parameter’s resolution. (See
"Complete Parameter List for ACS510" section for parameter resolutions.) For
example:
Where parameters are in percent, the "Complete Parameter List for ACS510"
section specifies what parameter corresponds to 100%. In such cases, to convert
from percent to engineering units, multiply by the value of the parameter that defines
100% and divide by 100%. For example:
1. Assuming, for the sake of this example, that the Actual Value uses parameter 9908
MOT
NOM
SPEED
as the 100% reference, and that 9908 = 1500 rpm.
2. Assuming, for the sake of this example, that the Actual Value uses parameter 9907
MOT
NOM
FREQ
as the 100% reference, and that 9907 = 500 Hz.
Actual Value Mapping
See the user’s manual supplied with the FBA module.
Feedback
Integer
Parameter
Resolution
(Feedback Integer) * (Parameter Resolution) =
Scaled Value
1
0.1 mA
1 * 0.1 mA = 0.1 mA
10
0.1%
10 * 0.1% = 1%
Feedback
Integer
Parameter
Resolution
Value of the
Parameter that
defines 100%
(Feedback Integer) * (Parameter Resolution) *
(Value of 100% Ref.) / 100% =
Scaled Value
10
0.1%
1500 rpm
1
10 * 0.1% * 1500 RPM / 100% = 15 rpm
100
0.1%
500 Hz
2
100 * 0.1% * 500 Hz / 100% = 50 Hz
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: [email protected]